The University of Chicago
Safety Manual
Environmental Compliance Programs

Section 6.3

Underground Storage Tank Management Program


Please note that this program has a glossary.   The glossary contains the definitions for various terms used in the program.   These terms are highlighted in bold print the first time they appear in the body of the program.


Policy

The University of Chicago shall operate and maintain all underground storage tanks in accordance with regulations promulgated by the Environmental Protection Agency (EPA) and the Illinois Office of State Fire Marshall (OSFM) to prevent the release of the regulated substance.

Definition and Applicability

The EPA defines an underground storage tank (UST) as any tank, including the underground piping associated with the tank that has at least ten percent of its volume underground.  UST regulations apply to tanks storing petroleum or certain hazardous chemicals except as noted below:

Authority and Responsibility

Environmental Health and Safety is responsible for:

  1. Conducting tank closures and removals in conjunction with appropriate regulatory agencies;
  2. Providing guidance to departments installing new underground storage tanks;
  3. Notifying regulation agencies when there is a release of a regulated substance;
  4. Investigating and confirming all suspected releases of regulated substances;
  5. Supervising a certified or licensed contractor to measure the presence of a released regulated substance when one exists; and
  6. Coordinating an annual “line test” with the departments responsible for functional underground storage tanks.

Departments are responsible for:

  1. Providing calibration and routine maintenance to  release detection systems via a certified or licensed contractor;
  2. Keeping record of calibration and maintenance reports;
  3. Monitoring underground storage tanks at least once every 30 days for release of a regulated substance;
  4. Contacting Environmental Health and Safety prior to installation of a new underground storage tank;
  5. Contacting Environmental Health and Safety prior to closure or removal of any underground storage tank; and
  6. Financing the removal of underground storage tanks.

Tank Installation

Contact Environmental Health and Safety prior to installation of a new underground storage tank.  Environmental Health and Safety will provide guidance based on regulations set by the EPA, OSFM and City of Chicago Department of the Environment.

Release Detection

Release detection, also referred to as “monthly monitoring” shall be provided on all tank systems.  Release detection shall be capable of detecting a release from any portion of a tank and piping that routinely contains product. 

The system must be routinely calibrated, operated, and maintained in accordance with the manufacturer's instructions.  Calibration and routine maintenance is the responsibility of the department and shall be conducted by a certified or licensed contractor.  Records of all calibrations and maintenance shall be kept with the department and readily available for review by Environmental Health and Safety.

Tanks and tank systems shall be monitored at least every 30 days for releases.  Monitoring of the systems shall be conducted by a certified or licensed contractor with the exception of monthly inventory control, manual tank gauging, and automatic tank gauging.  Documentation of the monitoring shall be maintained by the department.  Monitoring can consist of the following “monthly monitoring” methods of detection.

Monthly Inventory Control

Product inventory control shall be conducted monthly to detect a release of at least one percent of flow-through plus 130 gallons on a monthly basis in the following manner:

Manual Tank Gauging

Manual tank gauging may be utilized as release detection for tanks less than 2,000 gallons if the following requirements are met:

Tanks of 550 gallons or less in capacity can use manual tank gauging as the only release detection method.  Manual tank gauging may be used for tanks that are 551 to 2,000 gallons for a period of ten years after the cathodic protection was installed on the tank and at the end of ten years, another form of leak detection is required.  All tanks between 551 and 2,000 gallons shall receive a precision tank test once every year.  All records for manual tank gauging shall be kept onsite for three years.  Manual tank gauging shall not be used as a method of release detection for tanks over 2,000 gallons or tanks that after passing only a non-invasive tank integrity assessment are upgraded using cathodic protection.  Manual tank gauging shall not be used on tanks installed after May 1, 2003.  If a tank is suspected of leaking and the variation between the beginning and ending measurements exceeds the weekly or monthly standards in Table B it is subject to the requirement of OSFM for reporting.  The criterion for suspecting a leak using Manual Tank Gauging is:

Normal Tank Capacity

Weekly Standard
(One test)

Monthly Standard
(Average of four tests)

550 gallons or less

10 gallons

5 gallons

551-1,000 gallons

13 gallons

7 gallons

1,001-2,000 gallons

26 gallons

13 gallons


Precision Tank Tightness Testing

Tank tightness testing shall be capable of detecting a 0.1 gallon per hour leak rate from any portion of the tank that routinely contains product while accounting for the effects of thermal expansion or contraction of the product, vapor pockets, tank deformation, evaporation or condensation and the location of the water table.  Tracer elements shall not be used when a leak is suspected.  There are four types of precision testing:

Automatic Tank Gauging

Automatic tank gauging may be used with an accuracy of 0.2 gallons per hour together with monthly inventory control.  Automatic tank gauging shall not be used if a release is suspected.  If automatic tank gauging equipment is going to be used to test for loss of product and conduct inventory control it shall meet the following requirements:

Vapor Monitoring                  

Testing or monitoring for vapors within the soil of the excavation zone shall meet the following requirements:

Groundwater Monitoring       

Testing or monitoring for liquids on the ground water shall meet the following requirements:

Interstitial Monitoring

Interstitial monitoring between the UST system and a secondary barrier immediately around or beneath it may be used, but only if the system is designed, constructed and installed to detect a leak from any portion of the tank that routinely contains product and also meets one of the following requirements:

Statistical Inventory Reconciliation

Release Notification and Investigation

Notification

Environmental Health and Safety shall notify regulating agencies within 24 hours for any of the following conditions: 

Investigation

Environmental Health and Safety shall immediately investigate and confirm all suspected releases of regulated substances requiring reporting within seven days using either of the following steps:

Closure of Underground Storage Tanks

Contact Environmental Health and Safety prior to closure or removal of any underground storage tank.  Environmental Health and Safety shall conduct tank closures and removals in conjunction with appropriate regulatory agencies.
 

Section 6 Index

 Table of Contents


Environmental Health and Safety
Issued: 12/27/04
Revised: 02/25/09