The University of Chicago
Safety Manual
Fire Safety Programs
Section 4.3
Fire Detection Systems
Please note that this program has a glossary. The glossary contains the definitions for various terms used in the program. These terms are highlighted in bold print the first time they appear in the body of the program.
All fire detection systems shall be inspected, maintained and tested in accordance with this policy.
Departments responsible for coordinating the fixed fire protection program are:
These departments are responsible for:
Environmental Health and Safety shall be responsible for:
Licensed Contractors are responsible for:
Contractors and sub-contractors are responsible for complying with these procedures.
Fire Detection System Components
This policy shall cover all components of fire detection systems including, but not limited to:
Where Fire Detection is Required
Fire Alarm systems are installed as needed on a per building basis. Buildings classified as institutional, schools, hotels, dormitories, and high-rises (greater than 80 feet) are required by City of Chicago code to have fire alarm systems installed.
The National Fire Protection Association (NFPA) under NFPA 72, code 6-3.4, the National Fire Alarm Code, requires the following for sleeping areas which shall be adopted by the University of Chicago:
“Where audible appliances are installed to signal sleeping areas, they shall have a sound level of at least 15 dBA above the average ambient sound level or 5 dBA above the maximum sound level having a duration of at least 60 seconds or a sound level of at least 70 dBA, whichever is greater, measured at the pillow level in occupiable area.”
Monthly Inspection and Testing
All fire detection systems shall be inspected and tested monthly. The monthly inspection and testing of fire detection systems shall be in accordance with Chapter 72 "National Fire Alarm Code" of the National Fire Protection Association (NFPA).
All fire detection systems shall be tested at least annually by a designated departmental employee (e.g., building engineer or electrician) or private contractor knowledgeable in the operations and function of the system.
Criteria for the annual testing shall be in accordance with Chapter 72 "National Fire Alarm Code" of the National Fire Protection Association.
The following test shall be conducted at 15 years and every 5 years thereafter.
Two fixed temperature detectors for every 100 present shall be removed and tested by an approved testing laboratory. The two fixed temperature detectors removed for testing shall be replaced with two new fixed temperature heat detectors. If the tested fixed rate temperature heat detectors fail, all fixed rate detectors in the building's fire detection system shall be replaced.
Fire Detection Impairment Policy
All fire detection systems and their components that require being shut down due to maintenance and/or testing shall follow the appropriate notification and fire watch procedures according to this policy and Appendix B - "Fire Alarm Maintenance Shutdown/Reactivation Procedures".
Before Shutdown
Shutting down fire detection equipment shall be planned and limited to an eight hour time period.
Before the shut down of fire detection equipment, the supervisor of the employee performing the work shall follow these procedures:
Notification Process
To obtain permission to shut down a fire detection system, contact Environmental Health and Safety at 702-9999 prior to the start of the project.
Before the shutdown of the fire detection equipment, a representative from Environmental Health and Safety shall:
Notify the City of Chicago's Office of Emergency Communications to inform them of the building’s 911 status;
Notify the University Police Dispatch Center to inform them of fire alarm impairment; and
Ensure proper steps are taken in training personnel responsible for fire watch procedures.
During the Shutdown – Fire Watch
During the shutdown of the fire detection equipment, a fire watch shall be implemented by the original person requesting the fire detection system to be shutdown. The individual performing the fire watch shall be trained by Environmental Health and Safety in the following:
The fire watch shall consist of the following during the impairment:
Restoring the System
Upon completion of the work, the supervisor of the employee performing the work or his/her designee shall be responsible for:
Upon notification of restored impairment, Environmental Health and Safety shall:
All monthly and annual testing reports of fire detection systems shall be maintained by Environmental Health and Safety. The appropriate department shall forward all monthly and annual testing, maintenance and inspection reports to Environmental Health and Safety.
Fire Alarm Deactivation/Reactivation Procedures
All fire detection systems shall be turned off and reset in accordance with procedures found in Appendix A - "Fire Alarm Deactivation/Reactivation Procedures".
Environmental Health and Safety
Issued: 01/24/96
Revised: 03/06/09